Manufacturer | INFORM |
Model | GTR 3KVA ONLINE W/BATT |
Capacity | 3 kVA /2.7kW |
Type | On-Line |
Input | Nominal Voltage: 220V/230V/240V; Minimum Voltage (at half load): 90V; Minimum Voltage (at full load): 180V; Maximum Voltage: 270V; Frequency: 45-65 Hz; Power Factor: >0,99; Current Harmonics: < 6 %. |
Output | Power factor: 0.9; Nominal Voltage: 220VAC (factory set & adjustable from LCD panel with 1V steps from 208V to 242V); Voltage Tolerance: ±1%; Nominal Current @220V: 13,6A; Wave Form: Pure Sine Wave; at 100% linear load: <1,5%; at 100% non-linear load :<3,5%; Frequency: 50Hz or 60Hz (adjustable from LCD Panel); Frequency Tolerance(battery operation): 0,005 %; Static Voltage Regulation (0%-100% load): 1%; Dynamic Voltage Regulation (0%-100% load): 5%; Crest Factor: 3:1; Overload:100% to 125% overload:10 min;125% to 150% overload:1 min; Overall Efficiency (AC-AC): 94%; Greenmode ( Ecomode ) Efficiency: > 98%. |
Alarms | Audible and Visual Alarm Warning: 41 different Alarm Messages |
Display | LCD Panel:“Load %, Input/Output/Bypass Voltages, Output Power ( W & VA ), Output Current, Output p.f., Battery +/- Voltage Values, Input / Output Frequency, DC Bus +/-Voltages, Remaining Back Up Time, Internal Temperature, Heatsink Temperature”; Event Log: 500pcs (control availability in detail from LCD panel). |
Battery | Type: Maintenance-free lead acid batteries; Recharge Time: < 6h - 8 h; Quantity per String: 14pcs 12V Batt; Voltage: 168VDC; Internal Batteries (Optional): 7Ah, 9Ah, 12Ah; Warning: Audible Buzzer through the end of Battery Discharge; Cold Start: Present. |
Environment | Voltage Tolerance: ±10%; Frequency Tolerance: 3Hz (adjustable from LCD panel between 0.5Hz to 5Hz); Transfer Time: 0 ms; Overload Capability: up to 175%; Overload Protection: Bypass transfer time is calculated by simulating a temperature related model of a fuse; Short Circuit Protection: Acts as the ideal current source during the short circuit time; Other Protection: Protection against excessive heat,voltage,current & Deep Discharge Protection; Operating Temperature: 0 ˚C.... + 40 ˚C; Storage Temperature: -15 ˚C.....+55 ˚C; Proposed Temp. to extend battery life: 20 - 25 ˚C; Humidity: < 95%; Maximum Altitude: 1000m; Audible Noise ( from 1m distance ): <50 dB; Protection Class: IP 20. |
Interface | Interface (Communication Ports): RS232 (standard), SNMP, Modbus and USB (optional); Dry Contact Port ( Option ): 5pcs from LCD Panel adjustable dry contact signals. |
Weight | - |
Standarts | EN 62040-1-1 (safety), EN 62040-2(EMC), EN 62040-3(Performance) |
Dimensions | 272 x 740 x 758mm |
Warranty | 24 Months |